The meter has international standard external dimension and 3-key gentle push switch setting, single row 4-LED display. The temperature error can correct, return difference can be adjusted, control precision is high.
I. Technical specification
1, Input type: PT100(-50.0~300.0C) NTC10K: B= 3435(-50.0~150.0C)
2, Accuraacy: ± 0.5%F· S ± 1B
3, Relay output contact capacity: ALM1: 16A/240VAC;
ALM2: 3A/240VAC
4, External dimension(mm): 76× 34× 72 hole size(mm): 71× 29
5, Working power: AC110~242V, 50/60HZ, power dissipation is less than 3W
6, Working environment: Temperature 0~50.0C, relative humidity≤ 85%RH, without corrode and strong electric radiation.
The inner parameters:
I. Technical specification
1, Input type: PT100(-50.0~300.0C) NTC10K: B= 3435(-50.0~150.0C)
2, Accuraacy: ± 0.5%F· S ± 1B
3, Relay output contact capacity: ALM1: 16A/240VAC;
ALM2: 3A/240VAC
4, External dimension(mm): 76× 34× 72 hole size(mm): 71× 29
5, Working power: AC110~242V, 50/60HZ, power dissipation is less than 3W
6, Working environment: Temperature 0~50.0C, relative humidity≤ 85%RH, without corrode and strong electric radiation.
The inner parameters:
Series | Prompt | Name | Set range | Remark | Ex-Factory |
1 | Lock | Electronic lock | 0~50 | When Loc=18, all parameters can be revised; When Loc≠18, all parameters can not be revised. | 18 |
2 | AL_1 | The upper limit alarm | PT100: -50.0~300.0C NTC10K: -50.0~150.0C | Please refer to "VI\alarm output" | 100 |
3 | AL_2 | The lower limit alarm | 50 | ||
4 | Hy1 | The upper limit alarm return difference | 0.1~20.0 | 1.0 | |
5 | Hy2 | The lower limit alarm return difference | 1.0 | ||
6 | SC | Measurement error modifier | ±20.0 | The measured value can be modified through increasing or decreasing this data. | 0 |
7 | dP | Decimal point | ON or OFF | ON:Open decimal point; OFF: Close decimal point; | OFF |
8 | Sn | Input type | NTC or Pt | NTC10K:NTC; PT100:Pt | PT |